相關安規
- JIS
- CNS
- IEC
- VDE
- DIN VDE 0298-4:2013
- UL
NEC(National Ectrical Code)
- Table 310.15(B)(16)
Allowable Ampacities of Insulated Conductors Rated 0 - 2000 Volts,
60° to 90°C (140° to 194°F) Not More Than Three Conductors
in Raceway or Cable or Earth (Directly Buried),
Based on Ambient Temperature of 30°C (86°F)
- Table 310.15(B)(17)
Allowable Ampacities of Single Insulated Conductors
Rated 0 - 2000 Volts, In Free Air,
Based on Ambient Air Temperature of 30°C (86°F)
- Table 310.15(B)(3)(a)
Adjustment Factors for More than Three Current-Carrying Conductors in
a Raceway or Cable.
Where the number of current-carrying conductors in a raceway or cable
exceeds three, the allowable ampacities shall be reduced as shown:
- Table 310.15(B)(2)(a)
Temperature Correction Factors
For ambient temperatures other than 30°C (86°F), multiply the allowable
ampacities shown above by the appropriate factor shown below.