跳至導覽 跳至搜尋

相關安規

  1. JIS
  2. CNS
  3. IEC
  4. VDE
    1. DIN VDE 0298-4:2013
  5. UL

NEC(National Ectrical Code)

Allowable Ampacities of Insulated Conductors Rated 0 - 2000 Volts, 
60° to 90°C (140° to 194°F) Not More Than Three Conductors 
in Raceway or Cable or Earth (Directly Buried), 
Based on Ambient Temperature of 30°C (86°F)
  • Table 310.15(B)(17)
Allowable Ampacities of Single Insulated Conductors 
Rated 0 - 2000 Volts, In Free Air, 
Based on Ambient Air Temperature of 30°C (86°F)
  • Table 310.15(B)(3)(a)
Adjustment Factors for More than Three Current-Carrying Conductors in 
a Raceway or Cable. 
Where the number of current-carrying conductors in a raceway or cable 
exceeds three, the allowable ampacities shall be reduced as shown:
  • Table 310.15(B)(2)(a)
Temperature Correction Factors
For ambient temperatures other than 30°C (86°F), multiply the allowable 
ampacities shown above by the appropriate factor shown below.