==75℃ Capacitance and Relative test of THHW== | ==75℃ Capacitance and Relative test of THHW== | ||
*Capacitance and | *UL 2556 6.5 Capacitance and relative permittivity | ||
*The relative permittivity (dielectric constant) of the insulation shall be determined after 1 d by means of the following formula: | *The relative permittivity (dielectric constant) of the insulation shall be determined after 1 d by means of the following formula: | ||
<php> | <php> | ||
| 第13行: | 第13行: | ||
*75℃ Capacitance and Relative test of THHW | *75℃ Capacitance and Relative test of THHW | ||
*30℃ Capacitance and Relative test of MTW | *30℃ Capacitance and Relative test of MTW | ||
==Apparatus== | ==Apparatus== | ||
*The apparatus shall consist of the following: | *The apparatus shall consist of the following: | ||
於 2016年7月4日 (一) 10:31 的修訂
75℃ Capacitance and Relative test of THHW
- UL 2556 6.5 Capacitance and relative permittivity
- The relative permittivity (dielectric constant) of the insulation shall be determined after 1 d by means of the following formula:
<php> εr=13,600*C*log(D/d) where r = relative permittivity C = capacitance in microfarads of the immersed 3050 mm (120 in) portion of the specimen D = measured diameter over the insulation, mm (in) d = measured diameter under the insulation, mm (in) </php>
- 90℃ Capacitance and Relative test of THW-2
- 75℃ Capacitance and Relative test of THHW
- 30℃ Capacitance and Relative test of MTW
Apparatus
- The apparatus shall consist of the following:
- a capacitance bridge capable of operating at a sinusoidal or nearly sinusoidal voltage at a frequency of 1000 Hz at 10 V or less, or 60 Hz at 3.15 kV/ mm (80 V/mil) of insulation thickness;
- a water tank capable of maintaining the water at the required temperature; and
- a temperature-measuring device with an accuracy of ±1°C.