== NEC(National Ectrical Code) ==
== NEC(National Ectrical Code) ==
# Table 310.15(B)(16)
*[http://goo.gl/EhzgQE Lapp NEC安全電流表]
* Table 310.15(B)(16)
  Allowable Ampacities of Insulated Conductors Rated 0 - 2000 Volts,  
  Allowable Ampacities of Insulated Conductors Rated 0 - 2000 Volts,  
  60° to 90°C (140° to 194°F) Not More Than Three Conductors  
  60° to 90°C (140° to 194°F) Not More Than Three Conductors  
  in Raceway or Cable or Earth (Directly Buried),  
  in Raceway or Cable or Earth (Directly Buried),  
  Based on Ambient Temperature of 30°C (86°F)
  Based on Ambient Temperature of 30°C (86°F)
# Table 310.15(B)(17)
* Table 310.15(B)(17)
  Allowable Ampacities of Single Insulated Conductors  
  Allowable Ampacities of Single Insulated Conductors  
  Rated 0 - 2000 Volts, In Free Air,  
  Rated 0 - 2000 Volts, In Free Air,  
  Based on Ambient Air Temperature of 30°C (86°F)
  Based on Ambient Air Temperature of 30°C (86°F)
# Table 310.15(B)(3)(a)
* Table 310.15(B)(3)(a)
  Adjustment Factors for More than Three Current-Carrying Conductors in  
  Adjustment Factors for More than Three Current-Carrying Conductors in  
  a Raceway or Cable.  
  a Raceway or Cable.  
  Where the number of current-carrying conductors in a raceway or cable  
  Where the number of current-carrying conductors in a raceway or cable  
  exceeds three, the allowable ampacities shall be reduced as shown:
  exceeds three, the allowable ampacities shall be reduced as shown:
# Table 310.15(B)(2)(a)
* Table 310.15(B)(2)(a)
  Temperature Correction Factors
  Temperature Correction Factors
  For ambient temperatures other than 30°C (86°F), multiply the allowable  
  For ambient temperatures other than 30°C (86°F), multiply the allowable  
  ampacities shown above by the appropriate factor shown below.
  ampacities shown above by the appropriate factor shown below.

於 2014年4月23日 (三) 09:56 的修訂

相關安規

  1. JIS
  2. CNS
  3. IEC
  4. VDE
    1. DIN VDE 0298-4:2013
  5. UL

NEC(National Ectrical Code)

Allowable Ampacities of Insulated Conductors Rated 0 - 2000 Volts, 
60° to 90°C (140° to 194°F) Not More Than Three Conductors 
in Raceway or Cable or Earth (Directly Buried), 
Based on Ambient Temperature of 30°C (86°F)
  • Table 310.15(B)(17)
Allowable Ampacities of Single Insulated Conductors 
Rated 0 - 2000 Volts, In Free Air, 
Based on Ambient Air Temperature of 30°C (86°F)
  • Table 310.15(B)(3)(a)
Adjustment Factors for More than Three Current-Carrying Conductors in 
a Raceway or Cable. 
Where the number of current-carrying conductors in a raceway or cable 
exceeds three, the allowable ampacities shall be reduced as shown:
  • Table 310.15(B)(2)(a)
Temperature Correction Factors
For ambient temperatures other than 30°C (86°F), multiply the allowable 
ampacities shown above by the appropriate factor shown below.