「Minimum Bending Radius」:修訂間差異
跳至導覽
跳至搜尋
新頁面: *300.34 Conductor Bending Radius. **The conductor shall not be bent to a radius less than 8 times the overall diameter for nonshielded conductors or 12 times the overall diameter for... |
無編輯摘要 |
||
| 第1行: | 第1行: | ||
*300.34 Conductor Bending Radius. | *NEC Articles 300.34 Conductor Bending Radius. | ||
**The conductor shall not be bent to a radius less than 8 times the overall diameter for nonshielded conductors or 12 times the overall diameter for shielded or lead-covered conductors during or after installation. For multiconductor or multiplexed singleconductor cables having individually shielded conductors, the minimum bending radius is 12 times the diameter of the individually shielded conductors or 7 times the overall diameter, whichever is greater. | **The conductor shall not be bent to a radius less than 8 times the overall diameter for nonshielded conductors or 12 times the overall diameter for shielded or lead-covered conductors during or after installation. For multiconductor or multiplexed singleconductor cables having individually shielded conductors, the minimum bending radius is 12 times the diameter of the individually shielded conductors or 7 times the overall diameter, whichever is greater. | ||
於 2016年8月26日 (五) 12:04 的最新修訂
- NEC Articles 300.34 Conductor Bending Radius.
- The conductor shall not be bent to a radius less than 8 times the overall diameter for nonshielded conductors or 12 times the overall diameter for shielded or lead-covered conductors during or after installation. For multiconductor or multiplexed singleconductor cables having individually shielded conductors, the minimum bending radius is 12 times the diameter of the individually shielded conductors or 7 times the overall diameter, whichever is greater.