  • UL 2556 6.5 Capacitance and relative permittivity
  • The relative permittivity (dielectric constant) of the insulation shall be determined after 1 d by means of the following formula:

<php> εr=13,600*C*log(D/d) where sample 4.6m εr = relative permittivity C = capacitance in microfarads of the immersed 4.6m portion of the specimen(μF) D = measured diameter over the insulation, mil d = measured diameter under the insulation, mil </php>

  • 24hr <10%;24-336hr<10%;168-336hr <5%
  • 90℃ Capacitance and Relative test of THW-2
  • 75℃ Capacitance and Relative test of THHW
  • 30℃ Capacitance and Relative test of MTW

Apparatus

  • The apparatus shall consist of the following:
    • a capacitance bridge capable of operating at a sinusoidal or nearly sinusoidal voltage at a frequency of 1000 Hz at 10 V or less, or 60 Hz at 3.15 kV/ mm (80 V/mil) of insulation thickness;
    • a water tank capable of maintaining the water at the required temperature; and
    • a temperature-measuring device with an accuracy of ±1°C.