| 第5行: | 第5行: | ||
εr=13,600*C*log(D/d) | εr=13,600*C*log(D/d) | ||
where | where | ||
sample 4.6m | |||
C = capacitance in microfarads of the immersed | εr = relative permittivity | ||
D = measured diameter over the insulation, | C = capacitance in microfarads of the immersed 4.6m portion of the specimen(μF) | ||
d = measured diameter under the insulation, | D = measured diameter over the insulation, mil | ||
d = measured diameter under the insulation, mil | |||
</php> | </php> | ||
*90℃ Capacitance and Relative test of THW-2 | *90℃ Capacitance and Relative test of THW-2 | ||
於 2016年7月4日 (一) 10:48 的修訂
75℃ Capacitance and Relative test of THHW
- UL 2556 6.5 Capacitance and relative permittivity
- The relative permittivity (dielectric constant) of the insulation shall be determined after 1 d by means of the following formula:
<php> εr=13,600*C*log(D/d) where sample 4.6m εr = relative permittivity C = capacitance in microfarads of the immersed 4.6m portion of the specimen(μF) D = measured diameter over the insulation, mil d = measured diameter under the insulation, mil </php>
- 90℃ Capacitance and Relative test of THW-2
- 75℃ Capacitance and Relative test of THHW
- 30℃ Capacitance and Relative test of MTW
Apparatus
- The apparatus shall consist of the following:
- a capacitance bridge capable of operating at a sinusoidal or nearly sinusoidal voltage at a frequency of 1000 Hz at 10 V or less, or 60 Hz at 3.15 kV/ mm (80 V/mil) of insulation thickness;
- a water tank capable of maintaining the water at the required temperature; and
- a temperature-measuring device with an accuracy of ±1°C.