*75℃ Capacitance and Relative test of THHW
*75℃ Capacitance and Relative test of THHW
*30℃ Capacitance and Relative test of MTW
*30℃ Capacitance and Relative test of MTW
==Apparatus==
*The apparatus shall consist of the following:
** a capacitance bridge capable of operating at a sinusoidal or nearly sinusoidal voltage at a frequency of 1000 Hz at 10 V or less, or 60 Hz at 3.15 kV/ mm (80 V/mil) of insulation thickness;
** a water tank capable of maintaining the water at the required temperature; and
** a temperature-measuring device with an accuracy of ±1°C.

於 2016年7月4日 (一) 10:30 的修訂

75℃ Capacitance and Relative test of THHW

  • Capacitance and Relative permittivity
  • The relative permittivity (dielectric constant) of the insulation shall be determined after 1 d by means of the following formula:

<php> εr=13,600*C*log(D/d) where r = relative permittivity C = capacitance in microfarads of the immersed 3050 mm (120 in) portion of the specimen D = measured diameter over the insulation, mm (in) d = measured diameter under the insulation, mm (in) </php>

  • 90℃ Capacitance and Relative test of THW-2
  • 75℃ Capacitance and Relative test of THHW
  • 30℃ Capacitance and Relative test of MTW

Apparatus

  • The apparatus shall consist of the following:
    • a capacitance bridge capable of operating at a sinusoidal or nearly sinusoidal voltage at a frequency of 1000 Hz at 10 V or less, or 60 Hz at 3.15 kV/ mm (80 V/mil) of insulation thickness;
    • a water tank capable of maintaining the water at the required temperature; and
    • a temperature-measuring device with an accuracy of ±1°C.