==75℃ Capacitance and Relative test of THHW== | ==75℃ Capacitance and Relative test of THHW== | ||
The relative permittivity (dielectric constant) of the insulation shall be determined after 1 d by means of the following formula: | *UL 2556 6.5 Capacitance and relative permittivity | ||
*The relative permittivity (dielectric constant) of the insulation shall be determined after 1 d by means of the following formula: | |||
<php> | <php> | ||
εr= | εr=41390/L*C*log(D/d) | ||
where | where | ||
sample:4.6m | |||
C = capacitance in microfarads of the immersed 3050 mm (120 in) portion of the specimen | immersed in water:3.05m | ||
εr = relative permittivity | |||
L = length of specimen immersed in water, m | |||
C = capacitance in microfarads of the immersed 3050 mm (120 in) portion of the specimen (F;remark μF) | |||
D = measured diameter over the insulation, mm (in) | D = measured diameter over the insulation, mm (in) | ||
d = measured diameter under the insulation, mm (in) | d = measured diameter under the insulation, mm (in) | ||
form:2015/12/16 UL 2556 Revised | |||
</php> | |||
==75℃ Capacitance and Relative test of THHW== | |||
*UL 2556 6.5 Capacitance and relative permittivity | |||
*The relative permittivity (dielectric constant) of the insulation shall be determined after 1 d by means of the following formula: | |||
<php> | |||
εr=13,600*C*log(D/d) | |||
where | |||
sample 4.6m | |||
εr = relative permittivity | |||
C = capacitance in microfarads of the immersed 4.6m portion of the specimen(F;remark μF) | |||
D = measured diameter over the insulation, mil | |||
d = measured diameter under the insulation, mil | |||
form:2013/11/12 mail | |||
</php> | </php> | ||
* 24hr <10%;24-336hr<10%;168-336hr <5% | |||
*90℃ Capacitance and Relative test of THW-2 | *90℃ Capacitance and Relative test of THW-2 | ||
*75℃ Capacitance and Relative test of THHW | *75℃ Capacitance and Relative test of THHW | ||
*30℃ Capacitance and Relative test of MTW | *30℃ Capacitance and Relative test of MTW | ||
==Apparatus== | |||
*The apparatus shall consist of the following: | |||
** a capacitance bridge capable of operating at a sinusoidal or nearly sinusoidal voltage at a frequency of 1000 Hz at 10 V or less, or 60 Hz at 3.15 kV/ mm (80 V/mil) of insulation thickness; | |||
** a water tank capable of maintaining the water at the required temperature; and | |||
** a temperature-measuring device with an accuracy of ±1°C. | |||
於 2016年12月22日 (四) 11:34 的最新修訂
75℃ Capacitance and Relative test of THHW
- UL 2556 6.5 Capacitance and relative permittivity
- The relative permittivity (dielectric constant) of the insulation shall be determined after 1 d by means of the following formula:
<php> εr=41390/L*C*log(D/d) where sample:4.6m immersed in water:3.05m
εr = relative permittivity L = length of specimen immersed in water, m C = capacitance in microfarads of the immersed 3050 mm (120 in) portion of the specimen (F;remark μF) D = measured diameter over the insulation, mm (in) d = measured diameter under the insulation, mm (in) form:2015/12/16 UL 2556 Revised </php>
75℃ Capacitance and Relative test of THHW
- UL 2556 6.5 Capacitance and relative permittivity
- The relative permittivity (dielectric constant) of the insulation shall be determined after 1 d by means of the following formula:
<php> εr=13,600*C*log(D/d) where sample 4.6m εr = relative permittivity C = capacitance in microfarads of the immersed 4.6m portion of the specimen(F;remark μF) D = measured diameter over the insulation, mil d = measured diameter under the insulation, mil form:2013/11/12 mail </php>
- 24hr <10%;24-336hr<10%;168-336hr <5%
- 90℃ Capacitance and Relative test of THW-2
- 75℃ Capacitance and Relative test of THHW
- 30℃ Capacitance and Relative test of MTW
Apparatus
- The apparatus shall consist of the following:
- a capacitance bridge capable of operating at a sinusoidal or nearly sinusoidal voltage at a frequency of 1000 Hz at 10 V or less, or 60 Hz at 3.15 kV/ mm (80 V/mil) of insulation thickness;
- a water tank capable of maintaining the water at the required temperature; and
- a temperature-measuring device with an accuracy of ±1°C.